IINSPECTION, MAINTENANCE AND FUNCTIONAL TESTING OF ONBOARD FIRE PROTECTION AND SAFETY EQUIPMENT
• Portable and Wheeled Fire Extinguishers
• Fixed CO₂ Systems HP / LP
• Fixed Foam Systems
• Water Mist and Sprinkler Systems
• Fixed Dry Chemical Powder Systems
• Fire Detection and Alarm Systems
• SCBA Breathing Apparatus
• EEBD Emergency Escape Breathing Devices
• Firefighter Outfits and Chemical Suits
• Breathing Air Quality Testing
| Equipment | Annual actions | IMO reference |
|---|---|---|
| Portable fire extinguishers | Inspect condition, corrosion, safety pin, seal, hose, pressure charge, weight or contents as applicable, and service records | A.951(23) |
| Fixed CO₂ HP/LP | Inspect cylinders tank, piping, nozzles, hoses, release controls, protected space integrity and instructions. Check charge when required by its separate schedule | 1318/Rev.1 |
| Fixed foam system | Inspect tanks, pumps, valves, piping, proportioning equipment, nozzles and controls. Perform required functional checks and foam analysis when due | 1432 §7.4 |
| Water mist / sprinkler | Inspect pumps, valves, piping, nozzles and filters. Perform required operational, alarm and water quality checks | 1432 §7.5 |
| Fixed dry powder | Inspect powder storage, pressure supply, hoses, piping, nozzles and controls. Verify readiness and perform prescribed tests | 1432 §7.9 |
| Fire detection and alarm | Functionally test detection systems, inspect all detectors, and check alarms, power supply and interfaces | 1432 §7.2 |
| SCBA | Inspect apparatus, cylinders, masks, hoses, harnesses and regulators. Perform required functional and air quality checks | 1432 §7.8 |
| EEBD | Inspect condition, seals, pressure indicators, expiry dates and accessibility follow OEM and flag requirements | SOLAS II-2/14, OEM |
| Fire hoses and hydrants | Inspect and operate hydrants; pressure test a rotating sample of hoses, completing all within five years | 1432 §7.1 |
| Fire pumps | Flow-test all fire pumps, verify pressure and capacity, and test emergency pump under required isolation conditions | 1432 §7.1 |
| Fire doors and dampers | Inspect condition and test required local remote operations | 1432 §7.6–7.7 |
| Firefighter outfits | Check completeness, condition and readiness follow the applicable maintenance schedule | 1432 §5.10 |
| Wheeled extinguishers | Inspect and service in accordance with manufacturer instructions | 1432 §7.12 |
| Portable foam applicators | Verify condition and perform required annual service checks | 1432 §7.11 |