IINSPECTION, MAINTENANCE AND FUNCTIONAL TESTING OF ONBOARD FIRE PROTECTION AND SAFETY EQUIPMENT

• Portable and Wheeled Fire Extinguishers
• Fixed CO₂ Systems HP / LP
• Fixed Foam Systems
• Water Mist and Sprinkler Systems
• Fixed Dry Chemical Powder Systems
• Fire Detection and Alarm Systems
• SCBA Breathing Apparatus
• EEBD Emergency Escape Breathing Devices
• Firefighter Outfits and Chemical Suits
• Breathing Air Quality Testing

Equipment Annual actions IMO reference
Portable fire extinguishers Inspect condition, corrosion, safety pin, seal, hose, pressure charge, weight or contents as applicable, and service records A.951(23)
Fixed CO₂ HP/LP Inspect cylinders tank, piping, nozzles, hoses, release controls, protected space integrity and instructions. Check charge when required by its separate schedule 1318/Rev.1
Fixed foam system Inspect tanks, pumps, valves, piping, proportioning equipment, nozzles and controls. Perform required functional checks and foam analysis when due 1432 §7.4
Water mist / sprinkler Inspect pumps, valves, piping, nozzles and filters. Perform required operational, alarm and water quality checks 1432 §7.5
Fixed dry powder Inspect powder storage, pressure supply, hoses, piping, nozzles and controls. Verify readiness and perform prescribed tests 1432 §7.9
Fire detection and alarm Functionally test detection systems, inspect all detectors, and check alarms, power supply and interfaces 1432 §7.2
SCBA Inspect apparatus, cylinders, masks, hoses, harnesses and regulators. Perform required functional and air quality checks 1432 §7.8
EEBD Inspect condition, seals, pressure indicators, expiry dates and accessibility follow OEM and flag requirements SOLAS II-2/14, OEM
Fire hoses and hydrants Inspect and operate hydrants; pressure test a rotating sample of hoses, completing all within five years 1432 §7.1
Fire pumps Flow-test all fire pumps, verify pressure and capacity, and test emergency pump under required isolation conditions 1432 §7.1
Fire doors and dampers Inspect condition and test required local remote operations 1432 §7.6–7.7
Firefighter outfits Check completeness, condition and readiness follow the applicable maintenance schedule 1432 §5.10
Wheeled extinguishers Inspect and service in accordance with manufacturer instructions 1432 §7.12
Portable foam applicators Verify condition and perform required annual service checks 1432 §7.11